Eaton UPS service in Toronto
Symetrix Canada is not the manufacturer of Eaton equipment. For a unit under warranty, check the warranty terms with the manufacturer first.
We maintain and repair Eaton and Powerware UPS systems in Toronto and the GTA, from 9155 towers to multi-module Power Xpert 9395 systems: preventive maintenance, battery strings, fans and capacitors, emergency repair. For each model, Eaton publishes two separate dates: when it stopped selling it, and when full parts and labour support ends.
Key facts
Eaton models we service
| Model | Rating | Sales status | Eaton service phase | Usual work |
|---|---|---|---|---|
| 9155 | 8 to 15 kVA [5] | Sold | Best efforts from 2034 [6] | Batteries, fans |
| 9355 | 10 to 30 kVA [7] | Sold [8] | Best efforts from 2033 [9] | Batteries, fans, capacitors |
| 93PM 208V | 10 to 200 kW [10] | Sold [11] | Generation 1 best efforts from 2032 [12] | Power modules, batteries |
| 9390 | 20 to 160 kVA [13] | Discontinued; Eaton names the 93PM as comparable [14] | Best efforts from 2027 at 208 V, 2028 at 480 V [15] | Batteries, capacitors, fans |
| Power Xpert 9395 | 225 to 1,100 kVA [16] | Sold [17] | Best efforts from 2033 [18] | Power modules, batteries, capacitors |
| BladeUPS | 5 to 60 kW [19] | Discontinued, end of life [20] | Best efforts from 2028 [21] | Blade modules, batteries |
The 93E, 20 to 60 kVA [22], has reached end of life, with the 9355 and 93PM as Eaton’s replacements [23].
Sold and serviced are two different dates
Eaton’s catalogue says whether a model is still sold. Its end-of-service-life table says how long Eaton supports it: Active means all parts and labour [4], and Mature means best efforts, with parts possibly limited and replacement recommended [24]. So a discontinued 9390 is still in Active service until 2027, and a 9355 that is still sold already has its best-efforts year. Plan repair or replacement from both dates.
Eaton’s maintenance schedule
Eaton’s 91PS/93PS guide splits the work. The site team checks every day that the air intakes and the exhaust are clear [25]. Every month, it washes or replaces the optional air filters and writes the results in a service log [26]. Service personnel inspect for overheating, with attention to bolted connections, which must be re-torqued periodically [27].
What we check on an Eaton unit
- The event log, from the front panel or the network card, before any reset
- Each battery block’s voltage, internal resistance and temperature against its baseline [28]
- Bolted connections for heat, then torque with the equipment safely isolated
- Fan noise and airflow, capacitor condition, and the age of both
- Energy Saver System settings on models that offer it, such as the 93PM [11]
- The transfer to bypass and back, in your change window
Who to call
| Need | Who |
|---|---|
| A unit still under Eaton's warranty | Eaton first, under its warranty terms |
| A new three-phase unit to start up | Check the warranty: Eaton ties it to start-up by Eaton or its agent |
| Maintenance, batteries or repair outside warranty | Symetrix Canada |
| A model nearing its best-efforts year | Symetrix Canada, for a replacement plan built on Eaton's dates |
Common questions
Who services Eaton UPS systems in Toronto?
We maintain and repair Eaton and Powerware UPS systems across Toronto and the GTA, from single 9355 towers to multi-module 9395 systems.
How long does an Eaton UPS last?
The frame outlasts several battery strings. Eaton gives lead-acid UPS batteries 3 to 5 years [29], and recommends replacing power-train capacitors around 7 years of operation [1]. Full support runs until the model's best-efforts year; for the 9355 that is 2033 [9].
How do I reset an Eaton UPS?
Follow the reset procedure in your model's user guide, after saving the event log. A reset clears the alarm, not its cause. If the red alarm indicator stays lit, call service [30].
Is the Eaton 9390 still supported?
It is no longer sold, and Eaton names the 93PM as comparable [14]. Eaton keeps it in Active service until best efforts begin in 2027 at 208 V and 2028 at 480 V [15].
Do you service Powerware units?
Yes. Eaton's service table still files the 9355 under its Powerware line [9], and older Powerware three-phase models get the same visit as current Eaton ones.
Sources
- Eaton, Straight talk about capacitors in your UPS (WP153009EN), capacitor service life section
- Eaton, UPS fan replacement FAQs (SA161007EN), FAQ
- Eaton, Eaton 91PS/93PS UPS 8-40 kW User's and Installation Guide, P-164000493 rev 006, p. 16
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, legend, Active - Full Support
- Eaton, Eaton 9155 UPS, product overview
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p2, row 9155-8-10 (pdf.js row text)
- Eaton, Eaton 9355 UPS, product overview
- Eaton, Eaton 9355 UPS, page title; no discontinued label
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p4, row 9355-10-15: Active - Full Support 2009, Mature - Best Efforts 2033 (pdf.js row text)
- Eaton, Eaton 93PM 208V UPS, product snapshot
- Eaton, Eaton 93PM 208V UPS, product page; no discontinued label
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p4, rows 93PM-20-50 Gen 1 and 93PM 208V-20-60 (pdf.js row text)
- Eaton, Eaton 9390 UPS (discontinued), product snapshot
- Eaton, Eaton 9390 UPS (discontinued), product page banner
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p4, rows 9390-20-40 208V and 480V (pdf.js row text)
- Eaton, Power Xpert 9395 UPS family, family page, Power Xpert 9395 card
- Eaton, Power Xpert 9395 UPS family, family page, model cards
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p4, row 9395-275-275-CA (pdf.js row text)
- Eaton, Eaton BladeUPS (discontinued), product overview
- Eaton, Eaton BladeUPS (discontinued), product page banner
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p4, row BLADEUPS-12 (pdf.js row text)
- Eaton, Eaton 93E UPS (20-60 kVA), product snapshot
- Eaton, Eaton 93E UPS (20-60 kVA), product page banner
- Eaton, Eaton UPS End of Service Life (EOSL) Master Table, PL161010EN rev 05/29/2026, p1 legend (pdf.js row text)
- Eaton, Eaton 91PS/93PS UPS 8-40 kW User's and Installation Guide, P-164000493 rev 006, p. 110, section 8.3.1
- Eaton, Eaton 91PS/93PS UPS 8-40 kW User's and Installation Guide, P-164000493 rev 006, p. 110, section 8.3.2
- Eaton, Eaton 91PS/93PS UPS 8-40 kW User's and Installation Guide, P-164000493 rev 006, p. 110, section 8.3.3
- EnerSys, PowerSafe SBS XL Installation, Operation and Maintenance Manual, maintenance section
- Eaton, Lithium-ion UPS FAQ, FAQ
- Eaton, Eaton 91PS/93PS UPS 8-40 kW User's and Installation Guide, P-164000493 rev 006, p. 110, section 8.3.1
Eaton and the model names are trademarks of their owners, used only to identify the equipment we service.