How often should a data-centre UPS be serviced?

00:00:03.044 --> 00:00:06.757
Plan on a preventive maintenance visit at least once every year.

00:00:06.937 --> 00:00:12.429
Eaton recommends an annual mechanical review of the UPS and its battery cabinets.

00:00:12.609 --> 00:00:16.840
Vertiv's own service data supports 2 visits a year at critical sites.

00:00:17.020 --> 00:00:18.453
What happens during a visit?

00:00:18.633 --> 00:00:22.811
Our technicians measure every battery block, recording voltage,

00:00:22.811 --> 00:00:27.122
internal resistance and temperature: the IEEE practice for sealed

00:00:27.122 --> 00:00:30.371
lead-acid strings, 4 readings per block per year.

00:00:30.551 --> 00:00:33.558
We inspect and tighten the power connections at least

00:00:33.558 --> 00:00:36.564
once a year, following Vertiv's maintenance schedule.

00:00:36.744 --> 00:00:41.380
Fans and filters get checked, the event log gets read, and the static bypass

00:00:41.380 --> 00:00:45.894
gets a transfer test, booked in your change window under an agreed method.

00:00:46.074 --> 00:00:51.629
Infrared thermography sits on the same calendar: NFPA 70B, a standard

00:00:51.629 --> 00:00:56.942
since 2023, lists a thermal scan of all equipment every 12 months.

00:00:57.122 --> 00:00:58.289
What wears out, and when?

00:00:58.469 --> 00:00:59.422
Batteries first.

00:00:59.602 --> 00:01:02.340
Eaton puts lead-acid blocks at 3 to 5 years.

00:01:02.520 --> 00:01:06.315
A block that slips to 80 percent of its rated capacity is

00:01:06.315 --> 00:01:10.111
due for replacement; one that drifts more than 50 percent

00:01:10.111 --> 00:01:13.707
from its resistance baseline needs further evaluation.

00:01:13.887 --> 00:01:17.537
Around year 7, Eaton schedules a full replacement of the

00:01:17.537 --> 00:01:20.992
primary capacitors, and the fans go at the same time.

00:01:21.172 --> 00:01:25.034
And heat decides a lot: an average room of 35 degrees

00:01:25.034 --> 00:01:27.948
instead of 25 cuts battery life in half.

00:01:28.128 --> 00:01:30.598
Between visits, your own team keeps it simple.

00:01:30.778 --> 00:01:33.599
Every day, make sure the air intakes and the exhaust

00:01:33.599 --> 00:01:36.148
are clear, and that the green indicator is lit.

00:01:36.328 --> 00:01:40.422
Every month, check the air filters and write what you find in a service log.

00:01:40.602 --> 00:01:44.983
A red alarm lamp, or a green lamp that will not light, is a call for service.

00:01:45.163 --> 00:01:49.369
Symetrix Canada services UPS systems across Toronto, the

00:01:49.369 --> 00:01:53.649
GTA and Ontario, with an around-the-clock emergency line.

00:01:53.829 --> 00:01:56.275
Reply and quote within 4 business hours.

00:01:56.455 --> 00:02:00.109
Call 1 (438) 800-0382.

00:02:00.289 --> 00:02:04.426
Find Symetrix Canada on the web, at symetrixcanada.com.