00:00:00.000 --> 00:00:03.430
What does data-centre cleaning remove before electrical work?

00:00:03.610 --> 00:00:09.207
Two things that end up as faults: dust that clogs the filters and fans, and zinc whiskers,

00:00:09.207 --> 00:00:13.933
conductive filaments that grow on the undersides of some raised-floor tiles.

00:00:14.113 --> 00:00:17.207
Both come out with HEPA tools while the room stays live.

00:00:17.387 --> 00:00:18.744
What is the room collecting?

00:00:18.924 --> 00:00:22.617
Zinc whiskers first: the contamination guideline calls them

00:00:22.617 --> 00:00:25.935
the most common conductive particles in data centres.

00:00:26.115 --> 00:00:30.142
They stay put until a tile is lifted, then ride the airflow into

00:00:30.142 --> 00:00:34.044
equipment, where they can short circuits above about 25 volts.

00:00:34.224 --> 00:00:37.714
After them: construction dust in the plenum and the cable

00:00:37.714 --> 00:00:41.327
trays, packaging debris at the intakes, and corrosive gases

00:00:41.327 --> 00:00:44.512
that attack the copper and silver on circuit boards.

00:00:44.692 --> 00:00:45.694
What gets cleaned?

00:00:45.874 --> 00:00:49.650
The plenum under the floor first: debris out, then a HEPA vacuum

00:00:49.650 --> 00:00:52.954
and wipe of the slab, the pedestals and the cable trays.

00:00:53.134 --> 00:00:57.135
The tiles are cleaned on both faces, and tiles that shed whiskers are

00:00:57.135 --> 00:01:00.905
bagged where they lie and flagged for replacement, never brushed.

00:01:01.085 --> 00:01:05.539
Surfaces and equipment exteriors get anti-static wipes, top to bottom.

00:01:05.719 --> 00:01:09.793
The report carries before and after photos and the tiles to replace.

00:01:09.973 --> 00:01:10.880
When does it run?

00:01:11.060 --> 00:01:15.352
Before the UPS and cooling visits, so the new filters go into a clean room.

00:01:15.532 --> 00:01:20.003
That matters when filters change every 2 months, more often in dusty rooms.

00:01:20.183 --> 00:01:23.192
After any construction or fit-out is the other trigger.

00:01:23.372 --> 00:01:28.259
Dust on the UPS filters or in the plenum means the room is already overdue.

00:01:28.439 --> 00:01:31.003
Book the clean ahead of your next UPS window.

00:01:31.183 --> 00:01:35.389
Symetrix Canada services UPS systems across Toronto, the

00:01:35.389 --> 00:01:39.670
GTA and Ontario, with an around-the-clock emergency line.

00:01:39.850 --> 00:01:42.296
Reply and quote within 4 business hours.

00:01:42.476 --> 00:01:46.129
Call 1 (438) 800-0382.

00:01:46.309 --> 00:01:48.360
Find Symetrix Canada on the web.